What this ballast doesA fluorescent tube cannot run directly on line voltage: the
ballast starts the lamps and regulates their current. The TL432347-IS is an
instant start electronic ballast designed for 4 ft F32T8 tubes on 347V supplies. Compared with older magnetic ballasts, an electronic design runs at high frequency, which means quieter operation and less visible flicker. It is a component, not a light fixture: it mounts inside the channel of an existing troffer, wraparound or strip fixture.
Performance by number of lampsWith 4 F32T8 lamps, the ballast draws 109W at 0.322A with a
ballast factor of 0.87 and a power factor of 0.98. With 3 lamps, it draws 88W at 0.260A with a ballast factor of 0.94 and a power factor of 0.97. In both cases THD is 10% or less. It also works with T8 lamps of 32/25/17 and 30/28/25 watts, and its
parallel lamp operation keeps the remaining lamps lit if one tube fails, so a single burnt tube does not darken the whole fixture.
Wiring and installationTurn off the power, remove the old ballast and note the lamp holder connections. Leads are
18AWG: white and black 25", yellow 46", blue and red 31". For a three-lamp application, cap any unused blue lead and insulate it to 600V. Open circuit voltage is 600V, so work must be done by a
qualified electrician. Remote mounting is possible up to 18 ft. Keep the case at 90°C (194°F) or below, in an ambient of 55°C (131°F) or less. The spec sheet is available in the Documentation tab.
Technical specificationsModel: TL432347-IS
Type: instant start electronic ballast
Lamps: 3 or 4 x F32T8 (4 ft)
Input voltage: 347V, 50/60Hz
Input power: 109W (4 lamps), 88W (3 lamps)
Line current: 0.322A (4 lamps), 0.260A (3 lamps)
Ballast factor: 0.87 (4 lamps), 0.94 (3 lamps)
THD: 10% or less
Sound rating: A
Dimensions: 9.5" x 1.3" x 1.1", 8.9" mounting
Certifications: UL and cULus listed, Class P, Type 1 outdoor, Type HL
Warranty: 5 years at case temperature of 75°C or below, 3 years at 90°C or below
Where it is usedThis
347V ballast is common in office ceilings, school corridors, hospital wings and big-box stores across Canada. On 120V or 277V circuits, choose the
4-lamp 120-277V T8 electronic ballast instead, or the
2-lamp 120-277V model for
2 lamp T8 fixtures.